Mitsubishi 0403 Error Code

三菱空调错误代码

Code TextDescriptionCauseCheck Procedure
0403Serial Transmission Abnormality. Transmission fault between PCB’s in the outdoor unit.The fault occurs when there is a communication issue between PCB’s in the outdoor unit.-If the model number is a YMFB, YMFC or YEM-A then the fault is between the main board and inverter board.-If the model number is YGMA, YHMA, YJMA, YKMA or YLMA then the issue can be between the main board and inverter board or main board and fan board.Check for poor connections and broken wiring between the boards.If the unit is a YGMA, YHMA, YJMA, YKMA or YLMA check the error detail code using the dip-switches section of the app to determine which PCB’s the transmission fault is with. If the detail code is 1, then the issue is between the main board and inverter board. If the detail code is 5 then the issue is between the main board and fan board.Then check for poor connections between the PCB’s.

微信

Whats

Tel:347-987-6766

邮箱:jckhvac212@gmail.com

JK HVAC 我们安装、维修和保养所有品牌的空调!包括空调清洁、烘干机通风口清洁、暖气炉维修。