Code TextDescriptionCauseCheck ProcedureTechnical Support Notes
1301Low Pressure Fault.Low Pressure sensor (63LS) reads below 1 Bar in the system.Possible refrigerant leak. Restriction or blockage in refrigerant circuit causing low side pressure to drop. Problem with pressure sensor reading incorrectly.Check the system standing pressure for a complete gas loss.Use the Testing dip switches in the app and compare system gauge pressure to Low Pressure Sensor reading – If the pressure sensor is faulty it will read 0.0 bar even though there is pressure in the system.Using the testing dip switches check the system running pressures/temperatures to determine if the system is short of gas or if there is a restriction/blockage in the circuit.For refrigerant circuit diagram click the link below and type unit model number into the document library search box