包括三菱在内的空调制造商通常会在其用户手册中列出错误代码,供用户参考。如果您的设备手册已丢失,请查看下方列表,了解各型号三菱空调的错误代码。 Mitsubishi Error Code Lookup
三菱4位错误代码
Error Code Number | Air Conditioner Fault Description |
---|---|
0403 | Serial communication error |
0900 | Test run |
1102 | Discharge temperature fault |
1301 | Low pressure fault |
1302 | High pressure fault |
1500 | Refrigerant overcharge |
2500 | Drain sensor submergence |
2502 | Drain pump fault |
2503 | Drain sensor fault |
2600 | Water leak |
4102 | Open phase |
4106 | Transmission power supply fault |
4115 | Power supply signal sync error |
4116 | RPM error/Motor error |
4220 | Abnormal bus voltage |
4225 | Low bus voltage |
4230/4260 | Heatsink overheat protection activated |
4240 | Overload protection activated |
4250 | Overcurrent protection activated |
4255 | Outdoor unit fan error |
5101 | Temperature sensor fault |
5102 | Return air thermistor fault |
5110 | Outdoor unit inverter heatsink thermistor error |
5201 | Pressure sensor fault |
5301 | Current sensor fault |
5701 | Loose float switch |
6201 | Remote controller issue |
6600 | Address overlap |
6601 | Polarity setting error |
6602 | Transmission processor hardware error |
6603 | Transmission line busy |
6606 | Communication fault |
6607 | No ACK |
6608 | No response |
6831/6834 | MA controller signal reception error |
6832/6833 | MA controller comms fault |
7100 | Total capacity error |
7101 | Capacity code setting error |
7102 | Wrong number of connected units |
7105 | Address setting error |
7106 | Attribute setting error |
7110 | Signal transmission error |
7111 | Remote controller sensor fault |
7113 | Function setting error |
7117 | Model setting error |
7130 | Incompatible unit combination |
Mitsubishi Electric Air Conditioner Error Codes
Error Code Number and Letter | Air Conditioner Fault Description |
---|---|
P1 | Intake sensor error |
P2 P9 | Pipe (Liquid or 2-phase pipe) sensor error |
E6 E7 | Indoor/outdoor unit communication error |
P4 | Drain sensor error |
P5 | Drain pump error |
PA | Forced compressor error |
P6 | Freezing/Overheating safeguard operation |
EE | Communication error between indoor and outdoor units |
P8 | Pipe temperature error |
E4 | Remote controller signal receiving error |
Fb | Indoor unit control system error (memory error, etc.) |
E0 E3 | Remote controller transmission error |
E1 E2 | Remote controller control board error |
E9 | Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit) |
UP | Compressor overcurrent interruption |
U3, U4 | Open/short of outdoor unit thermistors |
UF | Compressor overcurrent interruption (When compressor locked) |
U2 | Abnormal high discharging temperature/49C worked/insufficient refrigerant |
U1 Ud | Abnormal high pressure (63H worked)/Overheating safeguard operation |
U5 | Abnormal temperature of heat sink |
U6 | Compressor overcurrent interruption/Abnormal of power module |
U7 | Abnormality of superheat due to low discharge temperature |
U8 | Outdoor unit fan safeguard stop |
U9 | UH Abnormality such as overvoltage or voltage shortage and abnormal synchronous signal to the main circuit/ Current sensor error. |
三菱 Mr. Slim-A 控制错误代码
- A0: Duplicate address; Lossnay units attached using the same address
- A2: Hardware error transmission processor
- A3: No data transmission for 8 minutes due to busy line
- A6: Communication error with processor; Lossnay address not being transmitted
- A7: No ACK signal
- A8: No M-Net response
- E0: Remote control transmission error (signal receiving error)
- E0-E5: Signal error between remote control and indoor units
- E1: Remote control communication issue
- E2: Remote control transmission error
- E3: Remote control transmission error (transmitting error)
- E3/E5: Remote control communication/receiving error
- E4: Remote control transmission error (signal receiving error)
- E5: Remote control transmission error (transmitting error)
- E6: Indoor and outdoor unit communication error
- E6-EF: Communication error between indoor and outdoor units
- E7: Indoor and outdoor unit communication error
- E8: Indoor and outdoor unit communication error
- E9: Indoor and outdoor unit communication error
- EA: Miswiring of indoor/outdoor unit (Exceeded the number of indoor unit connections)
- EB: Miswiring of indoor/outdoor unit (Miswiring disconnection)
- EC: Start-up time over
- ED: Serial communication error between boards on outdoor unit due to incorrectly fitted M-Net interface board
- EF: M-NET transmission error
- Ed: Serial transmission error
- F1: Reverse phase detection
- F1-FA: Outdoor unit error
- F2: L3 open phase detection
- F3: 63L connector open
- F4: 49C connector open
- F5: 63H connector open
- F7: Reverse phase detection circuit (P.C. board) fault
- F8: Input circuit fault
- F9: Connector 2 or more open
- FA: L2-phased open phase or 51CM connector open
- LED E0: Diagnosis of malfunction Transmitting / Receiving signal error
- LED Flash: Check code display
- LED LD1: LED ON Compressor directive / LED Flash Reverse phase detect
- LED LD2: LED ON Heating directive / LED Flash Open phase detect
- LED LD3: LED ON During 63H1 operation / LED Flash Pipe sensor short/open
- LED LD4: LED ON Compressor ON / LED Flash High pressure switch (63H2) operation
- LED LD5: LED ON Outdoor fan ON / LED Flash Over current relay (51CM) operation
- LED LD6: LED ON 4-way valve ON / LED Flash Thermal switch (26C) operation
- LED LD7: LED ON Bypass valve ON / LED Flash Thermistor (TH3) overheat protection
- LED LD8: LED ON Crankcase heater ON / LED Flash Defective input
- LED ON: Operation status
- LED P1: Intake air sensor abnormal
- LED P2: Pipe sensor abnormal
- LED P3: System error (transmitting/receiving signal)
- LED P4: Drain sensor abnormal
- LED P5: Malfunctioning of the drain overflow protecting mechanism
- LED P6: Abnormality of the coil frost / overheating protection mode
- LED P7: System error (address)
- LED P8: Outdoor unit malfunction
Mr.Slim K-control: PUH-EK Outdoor unit
- P1: Abnormality of room temperature thermistor (TH1)
- P2: Abnormality of pipe temperature thermistor/liquid (TH2)
- P4: Abnormality of drain sensor (DS)
- P5: Malfunction of drain-up machine
- P6: Freezing/overheating protection detect
- P8: Abnormality of pipe temperature
- P9: Abnormality of pipe temperature thermistor/condenser/evaporator (TH5)
- U0-UP: Outdoor unit error
- U1: Direct cut operation
- U2: Inner thermostat (49C) operation
- U3: Discharge thermistor short/open
- U4: Outdoor thermistor short/open
- U5: Inverter heat sink overheating
- U6: Compressor over current
- U7: Low discharge superheat (TH4)
- UA: Compressor overcurrent (terminal relay operation)
- UE: High pressure error (ball valve closed)
- UF: Compressor overcurrent (operating locked) cut off
- UH: Current sensor error
- UL: Abnormal low pressure
- Ud: Overheat protection
三菱 Mr. Slim 错误代码(薄膜型遥控器)
Check code | Diagnosis of malfunction | Cause | Check points |
EO | Signal transmitting/receiving error (Indoor controller does not respond to remote controller signal.) | During individual unit control 1) Bad contact of transmission wire 2) Signal transmitting/receiving cir- cuit is abnormal. | 1) Check the transmission wire. 2) Check with another remote controller. If “EO” is still indicated, replace the indoor controller board. If other check code appears. replace the origi-nal remote controller. |
P1 P2 | Abnormality of room temper- ature thermistor (RT1) Abnormality of indoor coil thermistor (RT2) | 1) Bad contact of thermistor 2) Damaged thermistor | 1) Check the thermistor. 2) Measure the resistance of the thermistor. Normal resistance should be as follows. 32°F····15kΩ 86°F·····4.3kΩ 50°F······9.6kΩ104°F·····3.0kΩ 68°F······6.3kΩ If the resistance is normal, replace the indoor controller board. |
P3 | Signal transmission error (Remote controller does not respond to indoor controller signal.) | 1) Bad contact of transmission wire 2) Signal transmitting/receiving cir- cuit is abnormal. 3) Wrong operation due to noise wave emitted by other appli- ances | 1) Check the transmission wire. 2) Check with another remote controller. If “P3” is still indicated, replace the indoor board. If other check code appears, replace the origi- nal remote controller. 3) Short-circuit between ¬ and Á of CN40 and attach CN40 to the following units. l Second unit in twin control l Second and third units in triple control l Sub units in group control |
P4 | Abnormality of drain sensor | 1) Bad contact of transmission wire 2) Damaged thermistor | 1) Check the connector. 2) Measure the resistance of the thermistor à – Ä. As for the normal resistance, refer to the case of P1. If the resistance is normal, replace the indoor con- troller board. |
P5 | Malfunction of drain pump | 1) Malfunction of drain pump 2) Damaged drain sensor | 1) Check the indoor/outdoor connecting wire. 2) Change the connection of electric wiring. 3) Check the protection device. 4) Measure the resistance of the outdoor coil ther- mistor. If the resistance is normal, replace the outdoor controller board. |
P6 | Coil frost protection is work- ing. | 1) Short cycle of air cycle 2) Dirty air filter 3) Damaged fan 4) Abnormal refrigerant | 1) Clear obstructions from the air cycle. 2) Clean the air filter 3) Check the fan. 4) Check the refrigerant temperature. |
P7 | System error | 1) Wrong address-setting 2) Signal transmitting/receiving cir- cuit of remote controller is abnormal. 3) Wrong SW6-setting | 1) Check the address-setting. 2) Check with another remote controller. If check code other than “P7” appears, replace the origi- nal remote controller. 3) Check SW6 setting. |
P8 | Abnormality in outdoor unit | 1) Wrong wiring of indoor/outdoor connecting wire 2) Reversed phase 3) Protection device is working 4) Damaged outdoor coil thermis- tor | 1) Check the indoor/outdoor connecting wire. 2) Change the connection of electric wiring. 3) Check the protection device. 4) Measure the resistance of the outdoor coil ther- mistor. If the resistance is normal, replace the outdoor controller board. |